Regufoam® Vibration Isolation

Regufoam® vibration is a mixed cell polyurethane foam for vibration isolation. It is available in 12 different qualities.

The technical data sheets are available for download in the password protected area. Register here to get access.

Regufoam® vibration 150 plus

View details
• permanent static load 0.011 N/mm² • optimum load range 0.004 - 0.011 N/mm² • tensile strength 0.31 N/mm² • mechanical loss factor 0.28 • static modulus of elasticity 0.06 - 0.16 N/mm² • dynamic modulus of elasticity 0.15 - 0.38 N/mm² • compression hardness 14 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for low permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 190 plus

View details
• permanent static load 0.018 N/mm² • optimum load range 0.011 - 0.018 N/mm² • tensile strength 0.4 N/mm² • mechanical loss factor 0.25 • static modulus of elasticity 0.1 - 0.25 N/mm² • dynamic modulus of elasticity 0.25 - 0.55 N/mm² • compression hardness 22 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for low permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 220 plus

View details
• permanent static load 0.028 N/mm² • optimum load range 0.018 - 0.028 N/mm² • tensile strength 0.5 N/mm² • mechanical loss factor 0.22 • static modulus of elasticity 0.15 - 0.35 N/mm² • dynamic modulus of elasticity 0.35 - 0.72 N/mm² • compression hardness 22 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for low permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 270 plus

View details
• permanent static load 0.042 N/mm² • optimum load range 0.028 - 0.042 N/mm² • tensile strength 0.9 N/mm² • mechanical loss factor 0.20 • static modulus of elasticity 0.25 - 0.45 N/mm² • dynamic modulus of elasticity 0.60 - 1.05 N/mm² • compression hardness 63 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for low permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 300 plus

View details
• permanent static load 0.055 N/mm² • optimum load range 0.042 - 0.055 N/mm² • tensile strength 1.2 N/mm² • mechanical loss factor 0.18 • static modulus of elasticity 0.35 - 0.58 N/mm² • dynamic modulus of elasticity 0.68 - 1.25 N/mm² • compression hardness 82 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for low permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 400 plus

View details
• permanent static load 0.11 N/mm² • optimum load range 0.055 - 0.11 N/mm² • tensile strength 1.5 N/mm² • mechanical loss factor 0.17 • static modulus of elasticity 0.6 - 1.0 N/mm² • dynamic modulus of elasticity 1.2 - 2.0 N/mm² • compression hardness 170 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for medium permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 510 plus

View details
• permanent static load 0.22 N/mm² • optimum load range 0.11 - 0.22 N/mm² • tensile strength 2.4 N/mm² • mechanical loss factor 0.15 • static modulus of elasticity 1.1 - 1.7 N/mm² • dynamic modulus of elasticity 2.2 - 3.7 N/mm² • compression hardness 330 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for medium permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 570 plus

View details
• permanent static load 0.30 N/mm² • optimum load range 0.22 - 0.30 N/mm² • tensile strength 2.9 N/mm² • mechanical loss factor 0.14 • static modulus of elasticity 2.6 - 2.9 N/mm² • dynamic modulus of elasticity 5.3 - 6.5 N/mm² • compression hardness 620 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for medium permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 680 plus

View details
• permanent static load 0.45 N/mm² • optimum load range 0.30 - 0.45 N/mm² • tensile strength 3.6 N/mm² • mechanical loss factor 0.12 • static modulus of elasticity 3.8 - 4.1 N/mm² • dynamic modulus of elasticity 7.0 - 10.0 N/mm² • compression hardness 840 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for high permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 740 plus

View details
• permanent static load 0.60 N/mm² • optimum load range 0.45 - 0.60 N/mm² • tensile strength 4.0 N/mm² • mechanical loss factor 0.11 • static modulus of elasticity 4.3 - 5.9 N/mm² • dynamic modulus of elasticity 8.9 - 13.0 N/mm² • compression hardness 1050 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for high permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 810 plus

View details
• permanent static load 0.85 N/mm² • optimum load range 0.60 - 0.85 N/mm² • tensile strength 4.6 N/mm² • mechanical loss factor 0.10 • static modulus of elasticity 5.4 - 8.0 N/mm² • dynamic modulus of elasticity 11.0 - 16.5 N/mm² • compression hardness 1241 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for high permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH

Regufoam® vibration 990 plus

View details
• permanent static load 2.50 N/mm² • optimum load range 0.85 - 2.50 N/mm² • tensile strength 6.9 N/mm² • mechanical loss factor 0.09 • static modulus of elasticity 20.0 - 78.0 N/mm² • dynamic modulus of elasticity 41.0 - 160.0 N/mm² • compression hardness 3640 kPa • fire behaviour B2, E

Areas of application

Vibration isolation and decoupling of structure-borne sound for very high permanent loads
Regufoam® Vibration Isolation BSW Berleburger Schaumstoffwerk GmbH